Question about Nofossil's simplest pressurized storage design

  • Active since 1995, Hearth.com is THE place on the internet for free information and advice about wood stoves, pellet stoves and other energy saving equipment.

    We strive to provide opinions, articles, discussions and history related to Hearth Products and in a more general sense, energy issues.

    We promote the EFFICIENT, RESPONSIBLE, CLEAN and SAFE use of all fuels, whether renewable or fossil.
Status
Not open for further replies.

Grovenburg

Member
Dec 9, 2011
50
[email protected]
I really like this simple design but have a question: When the load circulator calls for heat and the boilers are cold, the water goes in the bottom and out the top of storage. How does the water keep from circulating through the boilers as well?

I'm sure this is simple and I'm just missing something. thanks.
 
My circulators, Taco 007, have an integrated flow check (IFC) built into them. Oops, I forgot to add that I have several circulators. When the zone circs are calling and the boiler is cold the boiler/primary loop circ is off at that time. So it draws from the tank and returns to the tank.
 
My circulators, Taco 007, have an integrated flow check (IFC) built into them. Oops, I forgot to add that I have several circulators. When the zone circs are calling and the boiler is cold the boiler/primary loop circ is off at that time. So it draws from the tank and returns to the tank.

Do most circulators have IFC's? I have Grundfos 3 speeds and the check valves are in.
 
Do most circulators have IFC's? I have Grundfos 3 speeds and the check valves are in.

I do not know the answer to your question about if your Grundfos 3 has an IFC.

How many circulators do you have in the system? If your boiler is cold then the circulator for it will be off, I think that will prevent flow going through your boiler. Hopefully someone else will chime in and make sure I am correct about that.
 
Unless you removed the white plastic check valve from the discharge side it has a check valve.

gg
 
Two things:
  1. The flow check in the boiler circ provides a bit of reluctance - need enough pressure to crack the check valve
  2. The near tank plumbing should be arranged so that the preferred flow direction is through the tank. Hydrostatically speaking, the boiler loop should be a close approximation of closely spaced tees such that there is virtually no flow-induced pressure drop between the tees that connect the wood boiler to storage
 
Two things:
  1. The flow check in the boiler circ provides a bit of reluctance - need enough pressure to crack the check valve
  2. The near tank plumbing should be arranged so that the preferred flow direction is through the tank. Hydrostatically speaking, the boiler loop should be a close approximation of closely spaced tees such that there is virtually no flow-induced pressure drop between the tees that connect the wood boiler to storage

The wood boiler return mixing valve will not flow to load if mixing valve is cool. If using storage for power fail cooling then need mixing valve bypass and siphon circuit. Load circulator won't draw cool water from boiler if it has hot water right there at the top of the storage tank on account of hot water rises.
 