placement of OAK hole, in relationship tp the intake

  • Active since 1995, Hearth.com is THE place on the internet for free information and advice about wood stoves, pellet stoves and other energy saving equipment.

    We strive to provide opinions, articles, discussions and history related to Hearth Products and in a more general sense, energy issues.

    We promote the EFFICIENT, RESPONSIBLE, CLEAN and SAFE use of all fuels, whether renewable or fossil.
Status
Not open for further replies.

bostonfan49

Minister of Fire
Nov 10, 2011
531
Essex Jct. Vermont
Can the intake hole for the OAK (chimney) be the same height as the intake or does it need to be higher or lower! TIA, Bill
 
When installing my stove, it told me to place the OAK ( Air Intake Kit ) LOWER, than the 3" exhaust ( Flu Pipe ). So my fresh air intale is 5" below flu pipe & about 1 foot off side to side of flu pipe.
 
smwilliamson said:
Must be below and at least 12 inches away. Check in your stove manual.
Mine is obviously installed incorrectly, but seems to work fine. My OAK is about 4 inches from the exhaust hole, hut I also have about 5 feet of vertical rise of the pipe. I don't understand why the distance between the holes really matters. It seems like the only difference is the bigger the distance between the holes, the bigger the taint. Maybe for structural purposes? IDK.
 
smwilliamson said:
Must be below and at least 12 inches away. Check in your stove manual.

I've noticed a number of prefabbed combo units on here that do not follow the exhaust termination and OAK recommendations.

But back to Bill's question about where the hole comes through in relation to the air intake on the stove. There is one and only one rule there should be the least possible number of bends of any kind in the OAK. So a straight shot is always the best one.

Remember the above does not speak to any required distances from the vent termination. The recommendation is to have the OAK terminate below and at least as far as recommended by the stove's maker from the the exhaust vent as you can consistent with providing the most bend free shortest possible run to the stoves air intake.

In short read your stove's installation manual.
 
I could be wrong but I think I saw duravent thimbles for sale with oak outlet attached to bottom of thimble.
 
TLHinCanada said:
I could be wrong but I think I saw duravent thimbles for sale with oak outlet attached to bottom of thimble.

Nope you are not wrong, however those thimbles only provide proper OAK Vent termination separation if the vent continues upward after it exits the thimble outside the building. The so called out and up installation.

I've seen the OAK exit both below and above the vent exit on here so there are likely several different configurations. This is before some that I suspect were modified.
 
My manual for my Sante Fe says 12" below OR 12" above the exhaust for A CHIMNEY INSTALLATION. When I finally get up there to do mine, it will be probably 6-8" below but over a foot horizontally away from either of the two flues. (second one is from a 'spare' chimney that may get used when I get my wood fired antique cook stove (survival mode) finished
 

Attachments

  • tn_cook stove.jpg
    tn_cook stove.jpg
    38.3 KB · Views: 205
If I recall correctly. When I installed mine, I read the 12" separation is from the vent termination,
where the exhaust actually comes out, not 12" from the pipe itself. If you have a horizontal pipe out
you would need to be both below the exhaust point and 12" from the the exhaust point.
Heat rises and as such so does the exhaust. The intake being lower will bring in fresh air.
 
Status
Not open for further replies.