GF 15-55 alpha pump that I put on in late Sept 2014, started out at 45 watts and 11 gpm flow a couple days latter it "hung" at 30 some watts and 8/9 gpm for the past 2 + weeks it has stayed a 14/16 watts and 4/5 gpm, I have watch it very close and it even stays "there" when the floor is calling for heat (at which time a gf15-56 pulls the water thru a taco 4way , I have changed nothing my fluid is the same at 25% anti frez etc……… any body have this type pump and how’s it working out for u?
 
I am running GF Alpha pumps but they are not on auto adapt. Three are set on a particular speed, same gpm and wattage that they started with. One is set on a particular pressure (for thermostatically controlled radiator valves), which vary.
 
I talked to a tec at GF, he said its good to go ! saz "the system in their pump" ......found what "my system" needed ..and its working fine ... love the fact that I don't burn a bunch of juice /looking for the speed in which to run my system. if i'd had a regular 007 pump it would be running a lot more watts and speeds that are unneeded .
 
You could always compare supply and return temperatures and the gpm the pump is pumping against your heat loss calculation ... and comfort ... and have a good idea if it was adequate.
 
You could always compare supply and return temperatures and the gpm the pump is pumping against your heat loss calculation ... and comfort ... and have a good idea if it was adequate.
tell me more/how ....the temp is the same + or - a .5 deg, as it does its 120 loop
 
BTU/hr transferred by the water as it travels the loop = Gallons per minute * delta T * 500
So ... 4.5 GPM * 0 * 500 = 0 btu/hr ...
 