What pressure should I be running? Dripping Relief valve

  • Active since 1995, Hearth.com is THE place on the internet for free information and advice about wood stoves, pellet stoves and other energy saving equipment.

    We strive to provide opinions, articles, discussions and history related to Hearth Products and in a more general sense, energy issues.

    We promote the EFFICIENT, RESPONSIBLE, CLEAN and SAFE use of all fuels, whether renewable or fossil.
Status
Not open for further replies.

rombi

Member
Dec 17, 2007
112
Green Bay Wi
I have an Aquatherm that has been running for about 3 years with no problem.
The pressure safety valve started leaking a couple of days ago. I noticed my psi was about 12.
The system is a 150 run to the house where it goes to a HX in the basement. I talked to a HVAC guy and he said 10 was more than enough.
I just checked that relief valve and it looks like two drops out of it in 6 hours but I do not trust it anymore. $30 for a new one I guess.
 
mine are 30psi your pressure readings is that at full burn? cause I had mine a little high say 15psi and with a good hot burn it started to drip I just lowered my pressure and al is well.

Rob
 
At full burn it is about 12. It is a 30 valve on there.
I think I snagged the arm on the valve with my jacket ( I was cleaning behind stove) and that is when it started to drip.
I then opened it up and shut it but it still has a few drips overnight.
 
put a bucket under it and open the lever and let some water pass. see if you get any thing besides just water. You might have some scale, rust, flux whatever and that might have gotten under the rubber seal. After you flush it a little, open and close it a few times and maybe that will dislodge whatever is on the seal.
 
You should run at enough pressure to get water up to your highest radiator/convector air relief elevation in the house when the temp is the lowest it will go in the boiler. Anything more is really unnecessary unless you are so hot as to boil water, which isn't a good idea. 12 # works for me in my 2 story home w/ the boiler in the basement.

Mike
 
rombi said:
At full burn it is about 12. It is a 30 valve on there.
I think I snagged the arm on the valve with my jacket ( I was cleaning behind stove) and that is when it started to drip.
I then opened it up and shut it but it still has a few drips overnight.

I had one that leaked for better than a year after I bumped it . Try burping it a few times to clean it out let it a few days if it still drips , do it again and so on
as far as your pressure 12# should be fine and certainly not cause that to leak . Past experience mine use to start dripping at 26 #
As far as the valve , no worries probably still works fine , On the dripping note (PITA ),
If it is still dripping at the end of the heating season replace it .
Special note here
If you can burp this when your system is cool , because if hot you will reduce system pressure , not a real problem but by reducing system pressure you could possibly induce air into your system .
 
Thanks for the response guys. I do not know why I thought this thing needed to be up around 20psi?
It is a long run from the boiler to the house but it is a drop in elvation and then it is to a heat HX so there is no rise except for the re-run back to the pump.
It is still dripping a little. Enough to make me have a beer and watch it out there to see if I need another beer....
 
At least its a good night in Wisconsin for keeping beer cold in au natural
 
check your expansion tank. see if its water logged, if you don't have one, you should consider adding one.
the tanks are usually precharged for 12 psi. In order to check the pressure, you have to remove it from the system and check the precharge.

my $.02 of experience.