jimdeq

Member
Apr 23, 2010
205
northeastern wisconsin
Well, here it is. I finally have a fire roaring. 2 years of planning , building , and then rebuilding. The Tarm solo 60 in my attached garage with a 7'x11' enclosed boiler room with 5/8" firecode walls and a 36" steel fire door. I piped a 4" PVC fresh air intake with a U trap to the outside. 18' of 7" Hart & Cooley class A pipe. Boiler has a 8" collar,but I reduced it to 7" due to getting a great deal on the stainless pipe. I hope that 7"does not effect performance.
The pressurized storage consists of three 370 gallon glass lined hot water storage tanks I was able to obtain used,but in excellent condition. All pipeing is 1.25" and tanks are plumbed in reverse return. A 26-99 grundfos is used for the boiler circ and a grundfos Alpha is used for my zones. Zones consist of a coil in my forced air furnace, a sidearm exchanger on my DHW, and a zone for the shop loop which will be pumping to a stainless shell tube exchanger. The shop is 150' away with 1.25" thermopex buried 3 feet underground lying next to a 1.25" conduit with CAT 5E contoll wire. Shop is equipped with 6 loops of Hepex O2 barrier infloor tubing that are 270/ft each. 1.5" high density foam surrounds floor and sides of the grade beam slab.
I want to thank everyone who helped answer all my stupid questions over a two year period. I have to insulate the tanks and finalize controls yet,but my upstairs is 75 degrees right know. I will try to post more pics in the future.


Thanks for all your help.
 

Attachments

  • 100_2557.jpg
    100_2557.jpg
    16.7 KB · Views: 890
  • 100_2558.jpg
    100_2558.jpg
    24.3 KB · Views: 879
  • 100_2559.jpg
    100_2559.jpg
    35.7 KB · Views: 886
  • 100_2560.jpg
    100_2560.jpg
    26 KB · Views: 855
I bet that is making for a Very Merry Christmas ! congratulations....
 
Absolutely great. Real heat.

You may want to pay attention to sufficient air for the 60. The 4' PVC may not be enough, unless you have other air sources or leakage. A good indication will be whether you get any smoke out of the firebox when you open it to refuel, especially if it has not yet burned down to low coals. If you have sufficient air, you likely will not get any smoke roll-out; at least that's why I experience with my 40.

Wishing you a very Merry Christmas and Happy (and prosperous) New Year.
 
Very nice ! I really like the glass lined tanks.
 
I know your in that warm fuzzy feeling place right now, nice job. Merry Christmas and Happy Holidays to all. Sweetheat
 
Nice lookin setup. You will really love workin in the shop.
 
Congrats, looks great :)
 
Nice setup, nice tanks, those aren't easy to find. My only other thoughts are the large heat loss from tanks & piping(tanks you will insulate & the piping loss is in the shop) & 1000 gallons for that big boiler. You may want more storage in the future, Randy
 
With the surface area of those tanks exposed I'll bet its tee shirt and shorts weather in that room,nice looking set up but I'd want some insulation on those tanks
 
Thanks for all the nice comments. Jebatty stated that a 4 inch PVC might not be enough combustion air. I think he is correct because I do get alot of smoke roll out. The problem is that I have even tried opening the overhead door and still get rollout. My chimney is a foot taller than the roof peak and only two feet down from the peak. Any thoughts?
 
When loading after starting with a small fire. I have fan off and damper open. Open top door right away about 1 to 2" to get smoke to suck out of top box before opening more. While loading I keep door at 1-2" except for the time I'm actually putting in wood. By keeping the door partially closed you will get a better draft keeping wood box free of smoke. If I leave door open and go the few feet I need to go to get wood I will get roll out also.
 
RobC said:
When loading after starting with a small fire. I have fan off and damper open. Open top door right away about 1 to 2" to get smoke to suck out of top box before opening more. While loading I keep door at 1-2" except for the time I'm actually putting in wood. By keeping the door partially closed you will get a better draft keeping wood box free of smoke. If I leave door open and go the few feet I need to go to get wood I will get roll out also.

Good suggestions RobC. Also, it is likely that necking down to 7" chimney is not helping. I would recommend adding a four foot section to the top of the chimney too. Barometric damper? Try disabling or removing it, if you have one. Install looks great, happy heating! Chris
 