This Thursday I'm getting my Jotul Oslo installed!! I'm putting it in our basement. I'm thinking about just tiling right onto the concrete, I have some really nice tile that I'm using. I'm a little concerned about heat loss through the concrete. Should I put down some backerboard or some other product to help with insulation??
 
Directly under the stove I would think the heat loss would be minimal. More importantly is the rest of the floor and most importantly the walls. Is this a finished and insulated basement ??? If not, you are gonna lose a TON of heat to the outside. see below ....



http://www.woodstove.com/pages/basement_install.html

Shawn
 
True, most of the radiant heat will be projected out in front of the stove and upward. If this is a concern, there would be no harm in putting the hearth on an insulated pad. Also consider a raised hearth or platform. Air is a good insulator.
 
The concrete floor in my basement doesn't seem to warm up very much under my stove. Mine has an ash pan and you can put your hand on the bottom of the stove when the top is cooking at 500 F. That said, you can calculate expected loss using information provided in the ASHRAE 1981 Fundamentals Handbook, Chapter 25.7 table 4.

If the width of your house is 24 foot and the basement is five foot below grade, the floor heat loss coefficient is approximately 0.029 Btu/h ft^2 F. If your stove warms up a 60 F floor to 110 F, and you are heating 10 ft^2, then your heat loss from stove warming could be estimated ~ (0.029)*(10)*(110-60) = 14.5 Btu/hour.

Wider house or deeper basement would be slightly less loss. Narrower house or shallower basement would be slightly more loss. I am talking 10-20% when I say slightly. Of course, you can change the temperature and square footage to suit your circumstances.

In other words, don't worry about heat loss insulation under your stove.
 
Tile over concrete will be just fine. The purpose of hearth pads is to insulate the stove from a combustible floor. Most basement heat loss is via uninsulated walls.
 
Thank you, thank you, thank you! The basement is finished and walls are well insulated. I'm just going to tile right on top of the concrete.

God I love this website!!

Greg
 
gbailey1972 said:
Thank you, thank you, thank you! The basement is finished and walls are well insulated. I'm just going to tile right on top of the concrete.

God I love this website!!

Greg

But tell us how you really feel about hearth.com! ;)

Congrats on the purchase of the Oslo.
 