Storage tank manifold Question

  • Active since 1995, Hearth.com is THE place on the internet for free information and advice about wood stoves, pellet stoves and other energy saving equipment.

    We strive to provide opinions, articles, discussions and history related to Hearth Products and in a more general sense, energy issues.

    We promote the EFFICIENT, RESPONSIBLE, CLEAN and SAFE use of all fuels, whether renewable or fossil.
Status
Not open for further replies.

Attachments

  • 050.jpg
    050.jpg
    78.9 KB · Views: 262
  • 059.jpg
    059.jpg
    156.2 KB · Views: 287
Here's a three-tank setup:

http://summerwages.blogspot.com/


There's a manifold across the top and bottom. On the top between one end and the middle there's a tee for boiler supply, and between the other end and the middle there's a tee for load to draw from. And vice versa on the bottom.

If I had to do it again I wouldn't fool with the tees into the manifolds, I'd just run boiler supply into one end of the top manifold and pull load out the other end. And then use reverse return to bring load return into the opposite end of the bottom manifold and pull boiler return from the opposite end of the bottom manifold.
 