it is a new blader tank that we put in over the weekend but i didnt check charge on it ill do that tonight
After burning for a day i noticed that the wood boiler psi was up to 28psi, and then this moring with a cold system it was back down to 12-15psi, In...
its up to temps (180) and the dump zone kicked on the psi at the oil boiler is reading 15psi but the wood boiler looks to be closer to 18psi still...
So i just changed the expantion tank and the pressure reducing valve, after filling the system the pressure is about 16psi i just lit the wood boiler...
OK i do have an expantion tank with a blader, and looking around i did find the pressure reducing valve (dont know if thats correct) it says 12-15psi...
the pre set the on the oil boiler is says preset to 12psi and max of 75 but im not sure how to check that, and i dont know if this makes a differance...
I have an old Kerr wood boiler and we seem to have gotten everything to work but the prv drips when I load it for over night. It seems once the dump...
ok its been running for a few hours and seems to be working, the valve not being open all the way was most of the problem i also found that the dump...
The damper door does close. and both cirulators seem to turn on you can feel them running, ..... okay so thats what i started to type and then i...
Bought a new house end of last winter and used the wood boiler a few times with no issues, this year not so much. its an aux system tied into out...