I did find and seal a very small potential leak in the connection between the pellet stove and the chimney. And I sealed around the combustion gas...
There might be a very faint smell of smoke - more like "hot metal" if you know what I mean. My home - a boat - has a very small volume and a low...
Interesting idea ... the fan appears to be working well enough, but the CO levels do go down by a couple ppm if I run it on medium speed....
Sorry - I was not clear. Combustion air comes in through a duct - as you describe. Fresh air - for breathing - comes in around the door....
I was just thinking about that, but the answer is "not possible". I'm using a Testo 327 combustion analyzer to measure the ambient CO. It has...
Very interesting thread - similar story to mine. I also wonder how long I have been living with low CO levels without setting off the alarm....
Thanks for the idea - but the batteries are in the engine room - behind a weatherstripped door & vented to the outside. Andrew
The fresh air is pulled in around the door. It is somewhat sheltered from the chimney. I have thought this might be the issue, but even when...
Just in talking to Thelin today - all their units have a gap around the fan shaft - so that should not be the problem.
Thanks for the ideas. I do have a propane cook-stove, but it is not in use when I get the CO - it is directly related to the pellet stove....
Good morning, I have a 4 year old Thelin Gnome pellet stove installed in a 40 foot boat. I use a pipe to bring in outside combustion air. The...