Is insulation needed on my flex liner?

  • Active since 1995, Hearth.com is THE place on the internet for free information and advice about wood stoves, pellet stoves and other energy saving equipment.

    We strive to provide opinions, articles, discussions and history related to Hearth Products and in a more general sense, energy issues.

    We promote the EFFICIENT, RESPONSIBLE, CLEAN and SAFE use of all fuels, whether renewable or fossil.
Status
Not open for further replies.
I've decided to use a 4" x 20' Flex King Pro liner in my centrally located masonry flue.

The Mt. Vernon manual shows insulation only in the damper area, not on the flex liner itself.

The Flex king Pro brochure suggests using an insulation kit with the liner.

Is insulating below the chimney cap and using a block off plate and insulation in the damper area sufficient?

Is the insulation really necessary on the liner?

Suggestions please for the best setup.

Thanks in advance for any advise/comments. All are appreciated.
 
Could you explain your reasoning for it not being needed?

I'm sure others may disagree but I would also like their opinions of why it should be insulated. I'm not trying to stir the pot, There is a lot of knowledge and experience on this forum and I'm just trying to get educated.

Again, thanks for taking the time to reply.
 
I've decided to use a 4" x 20' Flex King Pro liner in my centrally located masonry flue.

The Mt. Vernon manual shows insulation only in the damper area, not on the flex liner itself.
To keep the room air that was just heated from wafting up the chimney, I highly recommend Roxul fireproof insulation on the damper shelf and around the liner

The Flex king Pro brochure suggests using an insulation kit with the liner.
Chimney manufacturers are really pushing insulation as another item to sell.

Is insulating below the chimney cap and using a block off plate and insulation in the damper area sufficient?
Insulation in the damper area in a center chimney is sufficient.
Block off plates were designed for wood stove pipes that connected the wood stove to the chimney. This is an old method.
Nowadays liners go all the way up to the top of the chimney and are sealed at the top. This makes blocking plates not necessary unless stated in the appliance manual or by the town inspector. The inspector should go by the manual but you can always check with him to make sure.

Is the insulation really necessary on the liner?
I would suggest insulation around the liner on outside chimneys and uninsulated chases up the sides of the house. In this case the cold temps can cool the warm gases in the liner and cause the liner to plug up sooner and may create more frequent cleaning.
Inside center chimneys that are warm really do not have this issue.

Suggestions please for the best setup.

Thanks in advance for any advise/comments. All are appreciated.

Just my 2 cents
 
Don2222,

Thanks for the reply.

So, Roxul in the damper area only. Would Lowes or Home Depot have Roxul ?

I plan on using a tera- cota collinear cap uptop for the 4" flex vent and the 3" oak termination.
 
Don2222,

Thanks for the reply.

So, Roxul in the damper area only. Would Lowes or Home Depot have Roxul ?

I plan on using a tera- cota collinear cap uptop for the 4" flex vent and the 3" oak termination.


Our Home Depot started to carry the Roxul. Some lumber yards carry it too.

That is what we use. We run a 4" SS liner for the exhaust and 3" liner for the fresh air.
Then the Roxul for the insulation on the damper shelf and you have a top notch fireplace install.
 
Our Home Depot started to carry the Roxul. Some lumber yards carry it too.

That is what we use. We run a 4" SS liner for the exhaust and 3" liner for the fresh air.
Then the Roxul for the insulation on the damper shelf and you have a top notch fireplace install.

Alrighty. Thanks!
 
Anyone else have anything to ad?
 
Take pics please, I am doing the same project right now

Yes, would love to see how liner install goes. Might be doing one in the future here too.
 
Pellet stoves with induced draft don't need insulation to keep the vent hot For them to draft. Pellet stoves hove very low emissions while running so there is nothing to condense in a cool liner.

Great Answer! For what it's worth Rowdy, we have tons (no pellet pun intended) of different units installed in our area using un-insulated liners with no problems. It's not an outside exposed chimney, I doubt you will have any problems. Good Luck!!
 
According to code, at least here in PA, you dont need an insulated liner/pipe when going through an existing chimney. Insulating the chimney cap and damper would be sufficient enough to block the cold air from coming down or the hot air escaping out.

I use a 3 by 17 ft liner on my Mt. Vernon insert and this year I blocked off the damper area with unfaced fiberglass insulation. People have varying opinions on this method, so dont take my post as an endorsement, but just an FYI.

As a side note, my SS flex liner is single wall uninsulated (i believe 6mm thick) and the hottest I've measured it right at the stove connection was 260F.

There area few threads about the topic on hearth.com if you want to further read up about it.

https://www.hearth.com/talk/threads/when-is-it-ok-to-not-insulate-liner-block-off.84047/
 