Mantle Heat Shield Width

  • Active since 1995, Hearth.com is THE place on the internet for free information and advice about wood stoves, pellet stoves and other energy saving equipment.

    We strive to provide opinions, articles, discussions and history related to Hearth Products and in a more general sense, energy issues.

    We promote the EFFICIENT, RESPONSIBLE, CLEAN and SAFE use of all fuels, whether renewable or fossil.

bruce56bb

Feeling the Heat
Nov 18, 2005
336
Flint Hills of Kansas
I got tired of the the fan noise from my insert and replaced it with a VC Encore.

According to the manual, 24" is the minimum clearance to the mantle without a heat shield and I have 20".
My question: Does the mantle shield need to run the full length of the mantle (over 8')?
 

Attachments

  • stove.JPG
    stove.JPG
    174.7 KB · Views: 119
I got tired of the the fan noise from my insert and replaced it with a VC Encore.

According to the manual, 24" is the minimum clearance to the mantle without a heat shield and I have 20".
My question: Does the mantle shield need to run the full length of the mantle (over 8')?
No, it should exceed the stove width. You can make it the width of the fireplace opening. Maybe attach it to the lintel?
 
  • Like
Reactions: bruce56bb
I like the idea Bg, but I'm not sure how it would look? I was thinking a 4" wide shield mounted to the mantle, with a space between it and the mantle?
 
I like the idea Bg, but I'm not sure how it would look? I was thinking a 4" wide shield mounted to the mantle, with a space between it and the mantle?
That would work fine too.
Make it 8" wider than the stove on each side. There should be a 1" gap from the mantle and it should stick out past the mantel by an inch.
 
Last edited:
  • Like
Reactions: bruce56bb