Finally testing my storage tank today. A few things that I have noticed.
1. Takes a while to bring 1000 gallons of 62 degree water up to temp.
2. The top did heat fast but 5 hours later the return is still pulling 62 degree water off the bottom of the tank.
3. Danfoss is working as it should but at times the boiler will idle for a few minutes because the Danfoss is pretty much closed with 62 degree water on one side.
I have 162 degrees on the top and about 140 half way down 62 degrees near the bottom.
I used the Simple pressurized method with connections on opposite ends. Hot top/ closest to boiler and return bottom far end of tank.
Now that I see first hand how the tank heats and works down it is apparent that I could have connected to one end top and bottom as others from the site had told me.
gg