Hi there all, I have an older Sante fe that has been wonderful for me till today, Noticed a lot of pellets had filled the pot to overflowing it. after a thorough cleaning I turned it back on and waited, and waited and waited for pellets to drop, Nothing. I had this happen one other time and found the tube to vacuum switch plugged, not this time, I checked for vacuum and was pulling .15 IN-Wg according to my fancy tester from work, The switch is closing when checked with an ohm meter, all snap discs ohm good. So I dug around and in my papers I found one for the control box that told of the different settings for the control box, on the bottom of the page it says to put in setting #0 for diagnosis, so I did, the Combustion blower, convection blower and ignitor prove out for the 10 second cycle, but the auger didn't feed, I checked and there is no power coming out of box on terminal #10 to the auger. Inside the control box nothing looks burnt and the fuse is good, so my question is this, does anyone know what tanker, hotel or gizmo holding the PFM may be the culprit inside the box? I hate to spend a few hundred bucks if all i need to do is replace a triac, optoisolator, or 0.1uF, 400V capacitors, big words I found about these boards, but not the info I needed for my problem. I am going to try to contact Pantrol also as they built the board but figured I'd ask here too.
Thanks for reading and any info.
Den-Den
Thanks for reading and any info.
Den-Den