Hello all, brand new member, although I have spent the last week or two browsing all the threads here. I keep coming back here to educate myself best I can. Here is my question and background:
I am finishing up restoring a 1902 Kalamazoo Wood Stove that was in my cabin. It has an 8" outlet on it and I plan on reducing it to 6" because my chimney measures approx 7" x 9" inside. Speaking of my chimney, it is masonry, 15ft. tall, and has the clay lining inside it. No noticeable cracks in the liner but some creosote buildup in there. Previous homeowner left me with a nice looking chimney sweep (I just moved bought the house 3 weeks ago) to clean it. The "pass through" for the pipe is an 11 3/4" x 11 3/4" steel lined box with an 8" diameter opening in the middle of it for the pipe.
I am going to be installing a fireboard behind and below the stove (room is made of logs) with the 1/2" clearance behind it to provide ventilation with the stove being placed 12-18" away from the fireboard. My question, as probably with most people: what is the cheapest and safest way to run chimney pipe? I ask because I have heard the following:
1) If my clay liner is fine, don't mess with it.
2) I need to re-line it with a new chimney liner (FlexKing, etc.).
3) I heard from a few old-timers who ran theirs for 25 years or more that they used stainless steel pipe dropped down the middle of clay lined chimney.
Option 3 sounds the best...The clay liner (once cleaned out) provides one aspect of protection and a stainless steel pipe (or single wall pipe) dropped in provides another layer of protection. Am I wrong to think this??? Please advise! Thanks!
I am finishing up restoring a 1902 Kalamazoo Wood Stove that was in my cabin. It has an 8" outlet on it and I plan on reducing it to 6" because my chimney measures approx 7" x 9" inside. Speaking of my chimney, it is masonry, 15ft. tall, and has the clay lining inside it. No noticeable cracks in the liner but some creosote buildup in there. Previous homeowner left me with a nice looking chimney sweep (I just moved bought the house 3 weeks ago) to clean it. The "pass through" for the pipe is an 11 3/4" x 11 3/4" steel lined box with an 8" diameter opening in the middle of it for the pipe.
I am going to be installing a fireboard behind and below the stove (room is made of logs) with the 1/2" clearance behind it to provide ventilation with the stove being placed 12-18" away from the fireboard. My question, as probably with most people: what is the cheapest and safest way to run chimney pipe? I ask because I have heard the following:
1) If my clay liner is fine, don't mess with it.
2) I need to re-line it with a new chimney liner (FlexKing, etc.).
3) I heard from a few old-timers who ran theirs for 25 years or more that they used stainless steel pipe dropped down the middle of clay lined chimney.
Option 3 sounds the best...The clay liner (once cleaned out) provides one aspect of protection and a stainless steel pipe (or single wall pipe) dropped in provides another layer of protection. Am I wrong to think this??? Please advise! Thanks!