what is causing a slight propane smell in house?

  • Active since 1995, Hearth.com is THE place on the internet for free information and advice about wood stoves, pellet stoves and other energy saving equipment.

    We strive to provide opinions, articles, discussions and history related to Hearth Products and in a more general sense, energy issues.

    We promote the EFFICIENT, RESPONSIBLE, CLEAN and SAFE use of all fuels, whether renewable or fossil.

jeanw

Feeling the Heat
Hearth Supporter
Sep 23, 2008
389
ky
In the last few weeks when the furnace comes on I can smell slightly propane smell seems to be coming thru the floor registers. This "package unit" is outside the house. It was here when we moved in several yrs ago. Hubby no longer spends enough time here to use the Hardy and he said when he is here occ he didn't smell anything..
Couple yrs ago had the furnace fan replaced, It was full of mud DOBBER mud. THE unit was used much since we used the Hardy. and didn't use he AC part of unit n much either The AH was supposedly to leave it here so we could look at the older fan ourselves. After they installed the new over $600 unit and service call. then last y Hubby sent for new Heat changer but after taking itnout and looking throughly at it and a different professional HVAC guy.. They reinstalled the old heat exchanger and returned the NEW Heat exchanger to parts distributor. The HVac guy also checked it out what Hubby did himself. At that time Hubby was hoping to sell this house here.. This house is in a semi rural area. smaller town in KY...
well since Im back at this house more started using furnace more( I decided I like this location better)
So hubby last week got hold of the nice HVAC guy and he came out and checked all of it including the AC part. He only worked on the outside didn't come in the house,
well since we have had so much nice temperatures lately have turned down thermostat to say 60... since Im outside so much lately gardening stuff.
SO y'all think the HEAT EXCHANGER may be cracked now? or what else?
will buying a small portable propane "snifter" help? any certain brand y'all recommend for me to buy and keep myself?. The HVAC guy didnt have one.
Help with suggestions y'all. ??? Hubby has a freon leak dector but the HVAC guy said it wouldn't work for detecting propane... Is that correct?
THANKS ALL
 
Call the fire department immediately?
I agree, get a professional in there to check it out--especially of you have any appliance that uses gas. If you don't the urgency may diminish as the mystery evolves, but either way better to figure it out. Gas leaks are a serious deal and can cause a big boom the next light that you turn on. Incidentally, this is why my new house has no gas in it, a house in my town turned to splinters after a gas leak! I recognize that my fear may be irrational, but I don't think so....
 
I, too, refuse to have gas in my house. A gas tech was in a nearby house's basement, along with the two owners. Something went wrong, and the house was reduced to matchsticks. One person killed, two hospitalized. Some buildings in Springfield, MA were destroyed a few years ago, when gas somehow got into their basements during construction across the street (!). The legal haggling was finalized, (I think) last year. I know, there are millions of buildings with gas in them that are perfectly safe, but life has enough hazards for me already. To each his own.
 
  • Like
Reactions: vinny11950 and Prof
I agree with the others, have it looked at ASAP. The part that worries me more than the gas smell though is the possibility of carbon monoxide in the cause of a cracked exchanger.

That being said there is nothing wrong safety wise with gas compared to any other fuel, literally every building in this part of the country is heated with it, very rarely do you ever hear of a fire or explosion from gas. I have 7 gas appliances in my house, I feel very comfortable about their safety, the threat of a chimney fire from my wood stove sometimes concerns me though. Carbon monoxide on the other hand kills a few people up here every year from improperly installed and maintained appliances.
 
if you don't have one already you should have a carbon monoxide detector. if the heat exchanger is cracked then the burn of the flame won't be right and you will have a high carbon monoxide reading in the house. a good heat guy will have a meter or fire dept should also have one
 
I just had my son read your post. He is a Canadian lic HVAC teck .
He says turn the heater off right now also turn off your propane supply
If you smell propane YOU HAVE A LEAK. Have the unit checked by
a lic teck and repaired
You are setting yourself up for a big boom
 
I agree, shut it down and have it looked at. The air path for the registers should be completely separate from the fuel burning path. You shouldn’t smell gas in the registers.

Just out of curiosity though how is your propane level? If you’re almost out, the substance they add to create the odor settles at the bottom of the tank and you’ll get more of it when you’re almost out.

I was afraid of gas in my old house after the dinosaur furnace (horizontal with an ambient long horizontal vent) almost killed me. I shut it down and switched to burning wood which saved me financially anyway. I also replaced the washer and dryer and went electric. I put in a new furnace with modern venting when I sold the house. The semi retired tech who set it up said they those ambient horizontal vented furnaces killed people and were outlawed in like the 70s.

My new house is mostly gas and I’ve learned how to be safe with it. But I only use gas for the small appliances and burn pellets for the heat. Gas costs a lot more for me when it comes to heat.
 
very rarely do you ever hear of a fire or explosion from gas.
Hmm...seems to be on the local and national news fairly often here...way too much IMO. Heck, half the town blew up a year or so ago when the gas company over pressurized the system in one NE state.
I agree, shut off the gas and get someone in there to check it out...my BIL/SIL have a large home with 2 HVAC systems...they had been having headaches with increasing frequency...finally they called the HVAC guy (not sure why exactly) he came in and said BOTH furnaces had cracked heat exchangers! I sure hope they have CO alarms now!
We rented an AIRBNB for vaca last year...got there and thought, hmm, this old house has a strange smell...wasn't strong enough to be obvious what the smell was. Seemed to be stronger through the night and I finally thought that it kinda has a gas smell to it. Went to the basement to have a look see the next morning and it was stronger down there...looked like a brand new furnace too.
Called the owner and he had the gas company come check it out...he said they didn't notice the smell, and their gas sniffer didn't even pick it up, but they sprayed a leak detector solution on all the pipe fittings and found one with a small leak...smell went away then. I personally felt I should have been given at least a partial refund...but nope, nothing...houses in this neighborhood are stacked a few feet apart too...a gas explosion would take out the whole block, not to mention just the fact that my family and I had all been breathing gas fumes for a day or so!

Anyways, get it checked out OP!
 
Call your local fire dept they will make a trip out for free and check things out and they are going to have the best equipment.. On a side note i have never seen a heating and cooling person not have a leak detector.. Ones i have used over the years always give things a sniff when they are done..
 
If you have propane the two must haves are a CO detector on every living level and a gas detector for propane the basement or lowest level.

As a firefighter I’ve seen more explosions from propane than natural gas because it sits low and you don’t smell it till it’s too late. Plus it’s explosive range is much sooner than Natural gas. Propane is explosive as low as 2% concentration where methane is 5%. 2% of a gas heavier than air is how your launched outta bed long before you smell anything. Propane ignites at a few hundred degrees lower than Natural gas also so it’s easier to have something as simple as an electrical arc ignite it compared to natural gas.

This was posted the other day. Have you had anything checked out to find out what it was?
 
Medic, any suggestions as to a good propane detector? Should I have one for the furnace and another for the water heater as they are about 25 feet apart?
I have a 1st Alert that plugs in with battery back up. It’s a combination with but but, co detections is not needed in the basement.

One should be adequate. They alarm befor an explosive level is reached.
 
  • Like
Reactions: woodey
Hmm...seems to be on the local and national news fairly often here...way too much IMO. Heck, half the town blew up a year or so ago when the gas company over pressurized the system in one NE state.

I guess American codes and standards are sub-par to Canadian ones. Gas fires or explosions just aren't common here, and in there rare case of one they are usually caused by someone hitting a buried line, or some homeowner trying to fix their own equipment without the knowledge to do so.

There are a few reasons in your Merrimack Valley example as to why that would be unlikely to happen here. Pressure safety valves are installed on equipment to prevent line over-pressure and vent the excess pressure. Regulators are also installed at every house to deliver consistent pressure regardless of line pressure. Emergency shutdown valves are also installed to shut in the supply should an over-pressure situation be detected.
 
when i put in carbon monoxide detectors the code up here in mass is one within twenty feet of a fuel burning appliance and one on every habitable floor and there should be one within ten feet of every bedroom but not in it. i asked my plumber about the gas explosions in the merrimack valley he said only the low pressure lines are effected. meaning if you are on high pressure gas you will have a regulator before the meter and most but not all are outside. if inside the vent for that regulator is piped to outside to vent the excess gas
 
I guess American codes and standards are sub-par to Canadian ones. Gas fires or explosions just aren't common here, and in there rare case of one they are usually caused by someone hitting a buried line, or some homeowner trying to fix their own equipment without the knowledge to do so.

There are a few reasons in your Merrimack Valley example as to why that would be unlikely to happen here. Pressure safety valves are installed on equipment to prevent line over-pressure and vent the excess pressure. Regulators are also installed at every house to deliver consistent pressure regardless of line pressure. Emergency shutdown valves are also installed to shut in the supply should an over-pressure situation be detected.
Almost every explosion I’ve ever seen that leveled the house was a direct result of someone’s error. The codes here are not subpar. The regulators have all the features you’re talking about.

The problem is people attempt to fix things like furnaces themselves. That’s where these tragedies begins.
 
  • Like
Reactions: bholler
I had a very faint gas odor right at the bottom of the stairs in the basement several years ago. It was the winter with 120" snow here west of Boston. There was a story on the news to clear snow off the gas meter outside your house. Mine was covered in snow. It is right outside the house where I had the very faint odor of gas.
 
Check the gas pipe fittings...specifically the union. They will get loose from vibrations that occur, such as passing traffic, if they aren't tight enough. Make sure to shut off the gas cock (valve) before any attempts to tighten, please!

Let us know what you find/found!


1589208016321.png union

1589208113916.png
gas cock (valve) or....
1589208163073.png
 
Almost every explosion I’ve ever seen that leveled the house was a direct result of someone’s error. The codes here are not subpar. The regulators have all the features you’re talking about.

The problem is people attempt to fix things like furnaces themselves. That’s where these tragedies begins.

If that were the case that gas explosion wouldn't have happened. The PSV on that section of piping would have opened releasing the pressure and avoiding the over-pressure situation that caused the explosion. Either there was no PSV, or the workers changing that regulator had in shut in so it wasn't operable.

I'm not sure how the legal side of this turned out, but if this would have happened here the workers on that line would have been facing charges of gross negligence causing death, and jail time if convicted.
 
well I haven't smelled any more propane in last couple of days. Hubby said the 3rd burner was taking longer to ignite. Yes I have a carbon monoxide detector only less than a year old
Plus"Tom from Utah" said they register CO2 too late. He calls on. RBN.org ( republicbroadcasting.org) various call in talk shows quite a bit, He is a pathologist etc and very involved, telling truth with CO2 problems in mobile homes venting one of his sites is https://www.gassingamerica.com
thanks all
 
well I haven't smelled any more propane in last couple of days. Hubby said the 3rd burner was taking longer to ignite. Yes I have a carbon monoxide detector only less than a year old
Plus"Tom from Utah" said they register CO2 too late. He calls on. RBN.org ( republicbroadcasting.org) various call in talk shows quite a bit, He is a pathologist etc and very involved, telling truth.... with this fake pandemic Ah I mean PLANDEMIC. .... also with CO2 problems in mobile homes venting one of his sites is https://www.gassingamerica.com
thanks all
Yes some co detectors do not go off soon enough in my opinion as well. But there are plenty of good ones on the market
 
If that were the case that gas explosion wouldn't have happened. The PSV on that section of piping would have opened releasing the pressure and avoiding the over-pressure situation that caused the explosion. Either there was no PSV, or the workers changing that regulator had in shut in so it wasn't operable.

I'm not sure how the legal side of this turned out, but if this would have happened here the workers on that line would have been facing charges of gross negligence causing death, and jail time if convicted.
When a homeowner decides to work on an appliance inside their house and something goes wrong you’re saying the homeowner, who’s usually dead in my experience, should face charges?

We must be talking about completely different situations Here. Every one of the dozen or so I’ve responded to in 25 years have been from a small leak that was caused by a homeowner doing work. One was a contractor who put in a ground rod next to the house and pierced the line before the regulator and it filled the basement through the perimeter drain. Another was actually a trencher went through an abandoned propane line that was still hooked to an “empty” tank. The residual propane found its way in the house and filled the basement.

Outside of a few pipeline emergencies here, I’ve never been on one outside of a contractor hitting one, most of these incidents are from inside work. Criminal charges for this type of stuff are almost impossible to make stick.
 
the carbon monoxide detectors that they say have to be hooked up and running for the gas inspection are slow on low trace amounts and if you go thru the paper work that is given with the detector it says it could take 2 to 4 hours to alarm. there is a chart for alarm. i think that is done to stop false alarms. really stupid in my opinion. it doesn't false alarm like a smoke detector. smoke detectors can be set off from a spider. carbon monoxide is there or it isn't
 
When a homeowner decides to work on an appliance inside their house and something goes wrong you’re saying the homeowner, who’s usually dead in my experience, should face charges?

We must be talking about completely different situations Here. Every one of the dozen or so I’ve responded to in 25 years have been from a small leak that was caused by a homeowner doing work. One was a contractor who put in a ground rod next to the house and pierced the line before the regulator and it filled the basement through the perimeter drain. Another was actually a trencher went through an abandoned propane line that was still hooked to an “empty” tank. The residual propane found its way in the house and filled the basement.

Outside of a few pipeline emergencies here, I’ve never been on one outside of a contractor hitting one, most of these incidents are from inside work. Criminal charges for this type of stuff are almost impossible to make stick.

I was referring to the Merrimack Valley and the explosion there. This was caused by the gas company, and what should have been qualified personnel, and yes those workers that caused the explosion would have likely faced criminal charges here, if it was because of poor practices and procedures management would have been on trial too.

Homeowners are totally different, you blow yourself up that's your own problem. That being said most people leave gas lines to the professionals, it's even taught in elementary school what gas lines are, what gas smells like, to get out of the house if you smell it, and to not touch or play with the lines. All our gas supply here is 7" WC, it takes a special kind of person to get leaks on that.
 
I was referring to the Merrimack Valley and the explosion there. This was caused by the gas company, and what should have been qualified personnel, and yes those workers that caused the explosion would have likely faced criminal charges here, if it was because of poor practices and procedures management would have been on trial too.

Homeowners are totally different, you blow yourself up that's your own problem. That being said most people leave gas lines to the professionals, it's even taught in elementary school what gas lines are, what gas smells like, to get out of the house if you smell it, and to not touch or play with the lines. All our gas supply here is 7" WC, it takes a special kind of person to get leaks on that.
That’s a standard pressure. Propane is 11.3-14 WC. Part of the problem is if you run a screw into a line in the wall you won’t hear the leak.