To test the vacuum switch turn it off using the c codes.
To adjust the operation constant, press and hold the MODE and AUGER DELAY buttons
simultaneously for 3 seconds. The display will show “C-1”. Use the HEAT RANGE UP or HEAT
RANGE DOWN buttons to change the constant number (see the list of values below). When the
desired constant is displayed, press the ON button to toggle between viewing and editing the value.
While editing a parameter, use the AUX UP and AUX DOWN buttons to adjust the values to the
desired point, then press ON again to return to the constant number list. Press the OFF button to
exit the adjust operational constants mode.
C-20- Ignore Vacuum Switch (0-1)- When this parameter is set to 1, the vacuum switch is
ignored. The default is 0 (do not ignore the vacuum switch).
Note only turn this off if you will be around to watch stove.
I do not have the stove but I
do not believe it has a high or low limit switch. High and low limits are based on Thermistor attached to exhaust which tells the control board the temp. Should be plugged into your control board and the other end should be bolted around exhaust motor housing. Check to see if it is plugged in tightly and bolted snugly.